Detailed description
Ⅰ.Features:
⊙ True RMS metering:
Measure all the
electric parameters such as voltage,current,frequency,active/reactive/apparent
power,power factor and etc.
⊙MONITORING:
1.power quality
2.Voltage harmonics 2-31st
3.Current harmonics 2-31st
4.Voltage crest factor
5.THFF(TIF)
6.Current k factor
7.Voltage unbalance factor
8.Current unbalance factor
9.Max/Min statistics with time stamps
⊙Communication:
standard RS-485 communication interface,which supports
Modbus-RTU protocol;
⊙I/O optional module:
A maximum of 3 modules can be used for one meter.
Digital input,digital output,pulse output,reply output, analog output are
provided by I/O option module.
ALARM:
Alarm contact for over voltage,under voltage,over
current.
⊙Harmonic:
the meter
measures component harmonics 2-31st inst and THD for both current
and voltage.
⊙time of use:
user can assign up to 4 different
tariffs(sharp,peak,valley and normal) to different time periods within a day.
2. Technical specification
Network
|
Three-phase three-wire、Three-phase four-wire
|
Rated voltage
|
AC 100V
400V(please instruct when order)
|
Voltage consumption
|
<1VA (each phase)
|
Voltage impedance
|
≥300KΩ
|
Voltage accuracy
|
RMS measurement、 accuracy class 0.5
|
Current
|
AC 1A 、5A(please instruct when order)
|
Current overloading
|
Continuance: 1.2 times, instaneous: 10 times/10s
|
Current consumption
|
<0.4VA (each phase)
|
Current impedance
|
<20mΩ
|
Current accuracy
|
RMS measurement、 accuracy class 0.5
|
Frequence
|
40~60Hz、 accuracy
0.1Hz
|
Power
|
Active power、Reactive
power、apparent power,accuracy class 0.5%
|
Electric power
|
Four quadrant
measurement,active accuracy 0.5%,reactive
accuracy 1%
|
Display
|
Programmable setting、switch-over、re-circle
3 lines LED displaying
|
Power supply working scope
|
AC/DC 85-275V or AC220V
|
Power consumption
|
≤5VA
|
Digital output interface
|
Standard RS-485、MODBUS-RTU Protocol
|
Pulse output
|
2-way power pulse
output
|
On-off value input (optional)
|
4-way on-off
value input
|
Alarm output(optional)
|
4-way on-off output,250VAC/3A
or 30VDC/5A
|
Analog output(optional)
|
4-way Analog
transmitting output,4-20mA DC
|
Working conditions
|
Temperature:-10~55℃
humidity:<85% RH
|
Storage condition
|
-20~75℃
|
Resist voltage
|
Input&power1600VAC,
Input&output1600VAC,output&power1600VAC
|
Insulation
|
input、output、power to shell>5MΩ
|
dimension(mm)
|
96*96mm 120*120mm
|
weight
|
0.5Kg
|